The DVC6200 is the upgraded successor to the Fisher DVC2000. Also HART-based, it supports full configuration, calibration and diagnostics via the 475 field communicator, and adds features such as an auto travel-calibration button and analog output activation. It suits all types of pneumatic control valves. This article organizes the complete DVC6200 commissioning workflow in five parts: 475 communicator calibration, guided setup (full initialization), feedback commissioning, auto-calibration button activation, and tuning.

Overview and Wiring

The DVC6200 is loop powered with 4–20 mA two-wire wiring, similar to the DVC2000: signal loop (IN+/IN-), position feedback output (separately supplied, 9–30 VDC) and limit switches (separately supplied, 4.3–30 VDC). HART communication connects through the signal loop.

Commissioning Procedure

Valve calibration with the 475 communicator

  • Enter the interface and select HART
  • Select Online, press Enter
  • If an alert is present, select YES and press Enter
  • From the Online menu select Configure, press Enter
  • Select the Calibration menu, press Enter
  • Select Auto Calibration
  • At the warning select Out of Service
  • Select CONTINUE, press Enter, then select Travel Control
  • The valve auto-calibrates; wait without operating anything
  • When calibration completes, confirm with OK
  • Return to In Service — calibration is finished

Guided setup calibration (full initialization)

  • Select HART → Online → Configure → Guided Setup
  • Select Device Setup; at the warning select Out of Service
  • Select pressure units (e.g. PSI)
  • Select amplifier type: A or C for single/double acting; B for reverse-acting positioners
  • Select Travel Control
  • Select Fisher as the actuator manufacturer
  • Select model and size from the actuator nameplate
  • Choose valve fails open or closed per your conditions
  • The positioner auto-detects the travel sensor direction
  • Specify whether quick-exhaust and flow amplifiers are present
  • Send the device setup data
  • Accept factory defaults with YES
  • Run the travel calibration: OK → YES
  • After auto-calibration completes, restore In Service

Feedback commissioning (analog output activation)

  • Configure → Manual Setup
  • Change mode protection from In Service to Out of Service
  • Select Outputs → Output Terminal
  • Select Enable, press Enter
  • Be sure to select Send to complete the setting
  • Return the valve to In Service

Activating the auto travel-calibration button

  • First set the valve to Out of Service
  • Manual Setup → Instrument → Terminal Box
  • Select Calibration Button, press the right key
  • Select Autocal, press Enter
  • Select Send to complete the setting

Tuning

  • Manual Setup → Tuning → Travel Tuning
  • Select Travel Tuning Set
  • Use the up/down keys to choose C–M (C slowest, M fastest)
  • Confirm the appropriate tuning
  • Be sure to click Send
  • Finally return the valve to In Service

Important: after all settings are complete the valve must be returned to In Service, otherwise remote control will not work.