RAGA Electric Actuators: Wiring & H01–H10 Parameter Commissioning Guide
source:    date:2026-09-29

RAGA is a Chinese actuator brand whose product line includes the RJ (modulating), RA2/RA3 (on-off), RQM (smart), RJM (compact) and RL (part-turn) types; wiring and commissioning are broadly common across models. This article focuses on RA-series on-off wiring and the H01–H10 parameter menu commissioning. Reference: RAGA actuator manuals and technical documentation.

RA On-Off Type Terminal Wiring

TerminalFunctionDescription
L1、L2、L3Three-phase supply380V
L、NSingle-phase supply220V
PEEarthProtective earth
5、35Remote open commandRemote open signal
5、33Remote close commandRemote close signal
6、7Fully-open signalPassive open-limit contact
8、9Fully-closed signalPassive close-limit contact

Wiring note: jumper terminals 5 and 34 (self-holding).

Commissioning Procedure (H01–H10 Parameter Menu)

RAGA actuators use menu-based parameter setting via the panel keys; parameters are numbered H01–H10:

ParameterNameDescription
H01Closing directionClockwise (CW) or counter-clockwise (CCW) closing
H02Remote priorityRemote/local control priority
H03Close limitSave the close limit at fully closed
H04Open limitSave the open limit at fully open
H05Closing torqueClosing torque as a percentage of rated
H06Opening torqueOpening torque as a percentage of rated
H07Input signal type4–20 mA / 0–10 V / 0–5 V etc.
H08Dead bandModulating dead band (percentage of stroke)
H09Feedback calibrationCalibrate the 4–20 mA position feedback output
H10Factory resetRestore all parameters to factory values

Commissioning workflow:

  • After energizing, enter the parameter setting mode (usually hold SET for 3 s or press the function key)
  • Set H01 (closing direction) first and confirm correct rotation
  • Run the valve fully closed and set H03 (close limit)
  • Run the valve fully open and set H04 (open limit)
  • Set H05 and H06 (close/open torque values)
  • Modulating actuators also need H07 (input signal type) and H09 (feedback calibration)
  • Verify over the full stroke and exit the setting mode once limits and feedback are correct