The panel menus and alarm messages of the 2nd-generation Rotork IQ/IQT electric actuators are in English; without a good grasp of these terms, fault-finding on site means repeatedly consulting the manual. This article translates the most-used IQ/IQT menu parameters — travel/torque, control and analog, alarms and status messages — term by term, then lists seven high-frequency field faults with symptoms and remedies in order of occurrence, as a quick reference for instrumentation and maintenance staff.
| Menu term | Meaning |
|---|---|
| TO / Torque Open | Opening torque |
| TC / Torque Close | Closing torque |
| CL Limit / Close Limit | Fully-closed limit |
| OP Limit / Open Limit | Fully-open limit |
| Direction | Direction setting (clockwise-close/counter-clockwise-open or the reverse) |
| Pos % Open | Valve position percentage (corresponds to the 4–20 mA feedback) |
Note: do not blindly raise TO/TC; if the valve sticks, check the mechanics first — do not just force the torque up.
| Menu term | Meaning |
|---|---|
| Analogue In | Analog setpoint (remote 4–20 mA command) |
| Analogue Out | Position feedback output (4–20 mA, terminals 22/23) |
| 4mA Point | Zero calibration (0% position) |
| 20mA Point | Span calibration (100% position) |
| Fail Mode | Signal-fail protection (Fail Last / Fail Open / Fail Close) |
Knowing these messages lets you judge the fault immediately when a critical actuator alarms:
| Menu term | Meaning |
|---|---|
| Torque Trip OP | Torque tripped in opening direction |
| Torque Trip CL | Torque tripped in closing direction |
| Torque Trip Mid | Torque tripped mid-travel |
| Motor Stall | Motor stalled (powered but shaft not turning) |
| Motor Over Temp | Motor over-temperature, thermal protection tripped |
| Lost Phase / Phase Fail | Phase loss (three-phase models) |
| Battery Discharged | Control-board backup battery flat (limits lost on power failure) |
| ESD Active | Emergency shutdown signal active |
| Interlock Active | Interlock engaged, operation inhibited |
| Mains Fail | Power supply lost |
| Config Error | Configuration error, parameters invalid |
Symptom: stops mid-travel with an alarm; cannot reach the end position on remote command. Checks:
Symptom: the actuator moves normally but the DCS position does not change or jumps. Checks:
Checks:
Checks:
Symptom: limits lost after a power outage, configuration scrambled, alarm at power-up. Remedy: replace the 9V backup battery on the control board and recalibrate the open/close limits (essential).
Symptom: motor hums, turns one way only, or trips immediately on energizing. Checks: three-phase supply lines, contactor contacts, fuses; verify phase sequence.
Symptom: powered but the output shaft does not turn, without a torque trip. Checks: clutch stuck in manual position, gearbox damage, or the valve seized.
Related reading: Rotork IQ Series: Terminal Wiring, Infrared Setter Commissioning & Troubleshooting; Universal Electric Actuator Wiring & Commissioning Guide; see also the Rotork brand column.