The Limitorque MX series from Flowserve (USA) uses the Modutronic electronic control unit; the QX series is the part-turn (quarter-turn) version with essentially the same commissioning method. Based on the MX commissioning manual, this article covers on-off and modulating terminal wiring and the complete commissioning procedure.
| Terminal | Function | Description |
|---|---|---|
| L1、L2、L3 | Three-phase supply | 380V three-phase; mind the phase sequence |
| PE | Earth | Protective earth terminal |
| 22、25 | Open command | Valve open command, remote via dry contact |
| 22、27 | Close command | Valve close command, remote via dry contact |
| 46、47 | Valve fully open | Open feedback signal |
| 44、45 | Valve fully closed | Closed feedback signal |
Wiring note: jumper terminals 21 and 28 (internal 24V supply).
| Terminal | Function | Description |
|---|---|---|
| L1、L2、L3 | Three-phase supply | 380V three-phase; mind the phase sequence |
| PE | Earth | Protective earth terminal |
| 20(+)、19(-) | Analog control command | Analog command 4–20 mA |
| 18(+)、17(-) | Analog feedback | Analog feedback 4–20 mA |
The main menu contains:
Note: normally both directions are set to POSITION. The close direction may be set to TORQUE if needed, but the open direction must never be torque seated.
Note: torque is factory-set to the valve's maximum; normally no change is needed. Over-setting can damage the valve stem or internal worm gearing.